System separator

Protect your drinking water from contamination by cooling lubricants. According to the Drinking Water Ordinance DIN EN 1717, every company is obliged to adequately protect its drinking water from contamination. With this system separator, you can guarantee this protection
for cooling lubricants and other chemical substances up to hazard class 4.

Maintenance
We recommend concluding a maintenance contract with an installation company.

Inspection
The inspection must be carried out every 6 months (depending on local conditions) by an installation company. A functional check
is carried out here
using a TKA295 or TK295 test device.

Maintenance
Maintenance must be carried out at least once a year (depending on local conditions) by an installation company or by the operator
. This involves removing the complete replacement unit
(article number 71001010) and replacing it with a new one.

Operational maintenance
If necessary, the integrated dirt trap can be removed, cleaned
or replaced

Faults / troubleshooting

Malfunction Cause Remedy
Drain valve opens without
reason
Pressure surges in the water network / fluctuating inlet pressure Install a pressure reducer upstream of the system separator
Drain valve opens without
reason
Cartridge insert is dirty Replace replacement unit
Drain valve does not close Deposits on the valve seat / Damaged O-ring / Leaking drain valve Replace replacement unit
Flow rate too low Strainer is clogged Clean the strainer
×